SCHED BANDWIDTH NOT AVAILABLE controlnet error problem

Question

What is the solution of SCHED BANDWIDTH NOT AVAILABLE message in ?

Answer ( 1 )

  1. Admin
    0
    2020-06-20T08:15:29+00:00
    This answer was edited.

    Error Code: 2 / 0x0002  -> SCHED BANDWIDTH NOT AVAILABLE

    Explanation / Possible Cause(s)

    • There are too many words scheduled for transmission
    • The network update time (NUT) is too small
    • The target node is not configured

    Possible Corrective Action(s)

    • Reduce the number of words scheduled for transmission
    • Increase the network update time (NUT)
    • Correctly configure the target node as an active node on the ControlNet network and save your ControlNet configuration
    Best answer

Leave an answer